- C110 D5, 110kVA Standby, 100kVA Prime, Enclosed Emergency Standby Power (ESP)
- Local Codes and/or Regulation : CE
- Output Voltage : 208/120, 3 Phase, Wye, 4 Wire
- Engine 6BTA5.9G5
- Engine Air Cleaner - Duty Rating : Normal Duty
- Engine Speed Governing : Isochronous Electronic Governor
- Main Generator: UC274C, 50 Hertz (Hz), 190 - 208V and 380 - 416V, 163C, Emergency Standby Power (ESP)
Generator Accessories
- Voltage Regulator - PMG
- Main Generator Heater : 240V
- Genset Housing: Sound Attenuated, Steel, Munsell Green
- Exhaust System - Silencer Grade : Enclosure Critical Cooling System, Genset Mounted Radiator, 50C / 122F, Genset Mounted
- Engine Coolant Mixture : 50% Antifreeze, 50% Water
- Primary Electrical Isolation Device - One Circuit Breaker
- Primary Electrical Isolation Device - 400A, 690V IEC, 3 Pole, 100%, Left Entrance Box / Terminal Housing
- Control System Options - PowerCommand 1.2
- Control Panel Mounting (Viewed From Generator End) : Left Facing
- Control Language : English
- Warning - Low Battery Voltage
- Shutdown - Low Coolant Level
- Display - Control LCD
- Emergency Stop Switch - External
- Starting Batteries: Lead Acid Batteries - Dry Charged Battery Charger, Set Mounted, 6A, 110 - 240 V
- Fuel Tank: In Skid, Single Wall, 350 Litres / 94 US Gallons, With Spillage Containment
- Fuel Tank Accessories - Fuel Level Alarms : Warning
- Warning Type : Low Fuel Level
- Genset Testing : Standard Factory Test
- Test Records : Certified Test Warranty
- Standby, 2 Years, 1000 Hours, Comprehensive Base Warranty
- Literature Language
- English Packing
Size | 110KVA |
---|---|
Voltage/ Current | 220V |